Modules are supplied with pattress fixing screws but are not supplied with IDRANet plugs (CON0002).
Visit the Accessories page for more information.

  ODO002 : Octal Digital Output

     
 
8 x 0-5V Uncommitted Logic Outputs (non-isolated, un-buffered)
 
Maximum current sink per output 20mA (80mA total)
 
Maximum source per output 1mA (5mA total)
 
All output states can be interrogated at any time
 
Highly flexible static output state modification
 
e.g. WRITE/SET/CLEAR/TOGGLE any group or individual
 
Module startup output states are user programmable
 
Powerful programmable dynamic output functions include:
 
Single shot: Delay, activity time, post activity state
 
Toggle: Period, duration
 
PWM: Mark, space, duty cycle
 
Status indicator LED
 
Fully IDRANet Compatible
 
Click arrow to download datasheet
     


       
  DIO002 : Quad Digital Input / Output

     
 
4 x 0-5V Digital Outputs (non-isolated, unbuffered)
 
Maximum current sink per output 20mA (80mA total)
 
Maximum source per output 1mA (5mA total)
 
4 x Digital Inputs (non-isolated)
 
All input and output states can be interrogated at any time
 
Highly flexible static LED state modification e.g. WRITE / SET / CLEAR /
    TOGGLE any group or individual
 
Module startup output states are user programmable
 
Powerful programmable dynamic output functions include:
 
Single shot: Delay, activity time, post activity state
 
Toggle: Period, duration
 
PWM: Mark, space, duty cycle
 
All Inputs can provide independent event triggers with mode programmable
    trigger gating : e.g. trigger on High->Low, trigger on Low->High, trigger on
    either transition, trigger and latch
 
Each event trigger can generate a predefined response and/or several user
    programmable responses
 
Status indicator LED
 
Fully IDRANet compatible
 
Module initialise trigger
 
Click arrow to download datasheet


       
  DRB002 : Dual 4A Relays/Buttons/LEDs/Inputs

     
 
2 x Click Effect Push Button Inputs
 
2 x Non-Isolated Digital Inputs (Filtered)
 
2 x LED Indicator Outputs
 
2 x Relay Outputs (SPNO 5A/230Vac fused at 4A with TVS protection)
 
Status indicator LED
 
All input and output states can be interrogated at any time
 
Highly flexible static output state modification e.g. WRITE / SET / CLEAR /
    TOGGLE any group or individual
 
Module startup output states are user programmable
 
Powerful programmable dynamic output functions include :
 
Single shot: Delay, activity time, post activity state
 
Toggle: Period, duration
   
PWM: Mark, space, duty cycle
 
All input devices can provide independent event triggers with mode
    programmable trigger gating : e.g. trigger on High->Low, trigger on
 
Low->High trigger on either transition, trigger and latch
 
Each event trigger can generate a predefined response and/or several user programmable responses
 
Module initialise trigger
 
Fully IDRANet compatible
 
Click arrow to download datasheet


       
  SRH002 : Single 10A Relay/Button/LED/Inputs

     
 
1 x Click Effect Push Button Input
 
2 x Non-Isolated Digital Inputs (Filtered)
 
LED Indicator Output
 
1 x Relay Output (SPCO 13A/230Vac fused at 10A with TVS protection)
 
Status indicator LED
 
All input and output states can be interrogated at any time
 
Highly flexible static output state modification e.g. WRITE / SET / CLEAR /
    TOGGLE any group or individual
 
Module startup output states are user programmable
 
Powerful programmable dynamic output functions include :
 
Single shot: Delay, activity time, post activity state
 
Toggle: Period, duration
 
PWM: Mark, space, duty cycle
 
All input devices can provide independent event triggers with mode
    programmable trigger gating : e.g. trigger on High->Low, trigger on
    Low->High, trigger on either transition, trigger and latch
 
Each event trigger can generate a predefined response and/or several user
    programmable responses
 
Module initialise trigger
 
Fully IDRANet compatible
 
Click arrow to download datasheet
 
How To Wire SRH-002 Modules


       
  DRH002 : Dual 13A Relays/LEDs/Inputs

     
 
2 x Non-Isolated Digital Inputs (Filtered)
 
2 x Relay Outputs (SPCO 13A/230Vac Non fused but with TVS protection)
 
LED Indicator Outputs
 
Status indicator LED
 
All input and output states can be interrogated at any time
 
Highly flexible static output state modification e.g. WRITE / SET / CLEAR /
 
TOGGLE any group or individual
 
Module startup output states are user programmable
 
Powerful programmable dynamic output functions include :
 
Single shot: Delay, activity time, post activity state
   
Toggle: Period, duration
   
PWM: Mark, space, duty cycle
 
All inputs can provide independent event triggers with mode programmable
    trigger gating : e.g. trigger on High->Low, trigger on Low->High, trigger on
    either transition, trigger and latch
 
Each event trigger can generate a predefined response and/or several user
    programmable responses
 
Module initialise trigger
 
Fully IDRANet compatible
 
Click arrow to download datasheet
 
How To Wire DRH-002 Modules


       
  QRI002 : Quad 4A Relays / LEDs / Inputs

     
 
4 x Non-Isolated Digital Inputs (Filtered)
 
4 x Relay Outputs (SPNO 5A/230Vac fused at 4A with TVS protection)
 
4 x Relay Indicator LED Outputs
 
Status indicator LED
 
All input and output states can be interrogated at any time
 
Highly flexible static output state modification e.g. WRITE / SET / CLEAR /
    TOGGLE any group or individual
 
Module startup output states are user programmable
 
Powerful programmable dynamic output functions include :
 
Single shot: Delay, activity time, post activity state
 
Toggle: Period, duration
 
PWM: Mark, space, duty cycle
 
All inputs can provide independent event triggers with mode programmable
    trigger gating : e.g. trigger on High->Low, trigger on Low->High, trigger on
    either transition, trigger and latch
 
Each event trigger can generate a predefined response and/or several user
    programmable responses
 
Module initialise trigger
 
Fully IDRANet compatible
 
Fits standard 35mm DIN rail, width 5M (88mm)
 
Click arrow to download datasheet


       
  QRH001 : Quad 13A Relays / LEDs / Inputs

     
 
4 x Non-Isolated Digital Inputs (Filtered)
 
4 x Relay Output (SPCO 13A/230Vac Non fused but with TVS protection)
 
4 x Relay Indicator LED Outputs
 
Status indicator LED
 
All input and output states can be interrogated at any time
 
Highly flexible static output state modification e.g. WRITE / SET / CLEAR /
    TOGGLE any group or individual
 
Module startup output states are user programmable
 
Powerful programmable dynamic output functions include :
 
Single shot: Delay, activity time, post activity state
 
Toggle: Period, duration
 
PWM: Mark, space, duty cycle
 
All inputs can provide independent event triggers with mode programmable
    trigger gating : e.g. trigger on High->Low, trigger on Low->High, trigger on
    either transition, trigger and latch
 
Each event trigger can generate a predefined response and/or several user
    programmable responses
 
Module initialise trigger
 
Fully IDRANet compatible
 
Fits standard 35mm DIN rail, width 6M (106mm)
 
Click arrow to download datasheet


       
  DFPH02 : Multifunction Display Panel


     
 
15 x Push Button Inputs
 
15 x Blue / Red backlights with brightness control
 
64 x 128 Pixel LCD display
 
LCD has RGB backlight and brightness control
 
2 x Concealed Tactile Buttons (e.g. for volume control)
 
PIR Detector 5m Range, 82°V x 100°H
 
Light Level Sensor (8bit)
 
Temperature Sensor (13bit, 0.03125°C res., +/-0.5°C)
 
Relative Humidity sensor (12bit, +/-2%)
 
2 x Independent Digital Inputs
 
4 x Relay drive outputs (suitable for 2 x XRM-001 Modules)
 
IR Receiver trainable to most handsets
 
16 x Onboard stores for arbitrary frame sets
 
IR Transmitter for control of 3rd party appliances
 
140 onboard stores for arbitrary frame sets
 
RC5 decoding / Direct synthesis of RC5 codes
 
'Hands Free' networked intercom :
 
Uses IDRANet audio bus allowing multi-way conversations
 
Network controllable: Hands free, receive only, transmit only
 
Network and locally controllable volume level
 
2 x Independent chronometers (with leap year correction)
 
2 x Independent interval timers
 
44 x different event triggers
 
Fully IDRANet compatible
 
Click arrow to download datasheet
 
How To Wire DFP-H02 Modules


       
  QAO002 : Quad Analogue Output

     
 
Number of channels: 4 (NON-ISOLATED)
 
Nominal output voltage range: 0V to +10V
 
Max. output current: 30mA per channel @10V, 50mA aggregate
 
Resolution over range: 10 bits monotonic
 
Internal update rate ~10Hz
 
Output levels can be set independently at any time
 
Simultaneous group settings possible
 

Independent Ramp function on each channel (8 bit resolution)

   
User selectable ramp rates: 0.04-5V / 0.1s or 0.04-5V / s
 

Independent User Defined Profiles for each channel (10 bit resolution)

   
Control over individual step dwell interval (range 0.1s - 127s)
   
No limit on profile lengths up to memory limits (>5K points)
   
Cyclic profiles and profile sharing possible
   
Profile data retained in non-volatile re-programmable memory
 

User definable initial output values

 

Module Initialise trigger

 

Status indicator LED

 
Fully IDRANet compatible
 
Click arrow to download datasheet


       
  SLD002 : Single 250W Light Dimmer

     
 
2 x Push Button Inputs
 
2 x LED Indicators
 
2 x General purpose LED Indicator Output
 
Status indicator LED
 
Maximum power: 250W incandescent (min 15W)
 
Voltage: 200-250V@50Hz AC
 
Electronic overload protected
 
Inherent soft start
 
Dimming range: 0-98% (power linearised)
 
Dimming Resolution: 0-255
 
Static or Dynamic output level can be set via IDRANet (or button) at any
 
time, allowing multiple unit scene setting via Cortex or by any networked
 
input device
 
Local control modes via onboard button
 
Ramp function with user definable rate
 
User definable free form dynamic profiles
   
Profile data retained in non-volatile re-programmable memory
   
Control over individual step dwell interval
   
Profile lengths up to memory limits
   
Cyclic profiles possible
 
User definable initial output value
 
Onboard push button and LED have full Reflex as well as local function
 
capability
 
Module Initialise trigger
 
Fully IDRANet compatible
 
Click arrow to download datasheet


       
  QLD001 : Quad 250W Light Dimmer

     
 
Designed to fit standard 35mm DIN rail (6M wide)
 
4 x 250W channels (leading edge phase control)
 
Output capacity 250W / 250Vac / 50Hz per channel
 
Fuse protected outputs
 
Thermal overload protection (self resetting)
 
Dimming range: 0-100% (power linearised)
 
Dimming Resolution: 8 bits (0-255)
 
Channel status indicator LEDs
 
Status indicator LED
 
8 x General purpose non-Isolated digital inputs (filtered)
 
Static or Dynamic output level can be set via IDRANet (or input) at any time,
 
allowing direct control or scene setting via Cortex or by any networked input
 
device
 
Digital inputs have full reflex as well as pre-defined local function capabilities
 
Independent channel ramp functions with user definable endpoints and rates
 
User definable free form dynamic profiles
   
Profile data retained in non-volatile re-programmable memory
   
Control over individual step dwell interval
   
Profile lengths up to memory limits
   
Cyclic profiles possible
 
User definable initial output states
 
Mains and over temperature trip status reporting to IDRANet
 
Automatic output level change reporting to IDRANet
 
Module Initialise trigger
 
Fully IDRANet compatible
 
Click arrow to download datasheet


       
  XRM001 : External Relay Module (for DFPH02)

     
 
2 x SPCO Relay Outputs
 
Fused at 4A/230Vac/30Vdc
 
Driven from DFPH02 rear connector
 
Click arrow to download datasheet
 
How To Wire XRM-001 Modules